Fault |
Possible cause |
Possible Solution |
---|---|---|
In the context menu Add Device the above symbol is displayed next to the TempScan. |
The device type has not been activated. |
Activate the device type TempScan (See operating manual of the PowerView3). |
The TempScan20 cannot be configured. |
The baud rate of the TempScan20 does not correspond to that of the PowerView3. |
Change the baud rate of the TempScan20 (refer to PowerView3 operating manual). |
|
The TempScan20 has been assigned with the wrong node ID in the PowerView3. |
Enter the correct node ID for your TempScan20 in the PowerView3 (refer to PowerView3 operating manual). |
Measured values are incorrect. |
Wrong thermocouple type settings |
Enter the correct thermocouple type in the PowerView3 (see section Settings in the PowerView3). |
The thermocouple is faulty. |
Replace the thermocouple (see section Connecting Thermocouples). |
|
A thermocouple does not display any measured values. |
The relevant channel is not activated. |
Activate the relevant channels in the PowerView3 (see section Settings in the PowerView3). |
The thermocouple is faulty. |
Replace the thermocouple (see section Connecting Thermocouples). |
|
The thermocouple is not connected properly. |
Connect the thermocouple correctly (see section Connecting Thermocouples). |
|
A threshold value cannot be set to the desired temperature. |
Threshold values are too close to each other. |
Threshold values must differ by a minimum of 10 °C (18 °F). |