No ignition sensor unit (ISU) is required when you use the ignition controller with ASO output from MOTORTECH (e. g. MIC4). In this case, the ignition pulse is transmitted to the DetCon via the auxiliary synchronization output (ASO). The jumper identified with Load Resistance must be removed.
Position Load Resistance Jumper The jumper Load Resistance changes the input resistance of the ignition input.
It is on the upper left of the device |
The connection between DetCon and the ignition controllers with ASO output is established as follows:
|
DetCon |
other equipment |
DetCon |
|
MIC850 connection |
MIC3, MIC4, MIC5 connection |
Configuration of the ignition controller In the configuration software (MICT) for the MOTORTECH ignition controllers with ASO output, the adjustments for the DetCon can be easily made using the button Configuration for DetCon2/20. This can be found on the configuration page Input/Outputs – ASO1 (auxiliary synchronization output). Further information can be found in the operating manual of your ignition controller. |